Experimental data for test 19 (31.6 kW, door 6/6 , fire location A) by Steckler et al. (1982) Temperature in the corner z [m], T [C], (-)err [C], (+)err [C] 0.057, 37.70, 4.0, 2.0 0.171, 38.00, 4.0, 2.0 0.285, 38.57, 4.0, 2.0 0.399, 39.04, 4.0, 2.0 0.513, 40.13, 4.0, 2.0 0.627, 41.64, 4.0, 2.0 0.741, 44.26, 4.0, 2.0 0.855, 49.71, 4.0, 2.0 0.969, 68.57, 4.0, 2.0 1.083, 82.92, 4.0, 2.0 1.197, 85.15, 4.0, 2.0 1.311, 85.75, 4.0, 2.0 1.425, 85.98, 4.0, 2.0 1.539, 85.93, 4.0, 2.0 1.653, 86.18, 4.0, 2.0 1.767, 86.51, 4.0, 2.0 1.881, 86.10, 4.0, 2.0 1.995, 86.12, 4.0, 2.0 2.109, 83.48, 4.0, 2.0 Temperature across the door z [m], T [C], (-)err [C], (+)err [C] 0.057, 31.50, 0.171, 31.35, 0.285, 30.14, 0.399, 30.50, 14.0, 2.0 0.513, 31.06, 14.0, 2.0 0.627, 31.45, 14.0, 2.0 0.741, 30.76, 14.0, 2.0 0.855, 31.23, 14.0, 2.0 0.969, 35.27, 14.0, 2.0 1.083, 50.76, 14.0, 4.0 1.197, 72.77, 14.0, 4.0 1.311, 77.88, 9.0, 4.0 1.425, 81.03, 9.0, 4.0 1.539, 82.38, 9.0, 4.0 1.653, 83.66, 9.0, 4.0 1.767, 86.01, 2.0, 4.0 Flow speed across the door z [m], u [m/s], (-)err [%], (+)err [%] 0.057, -0.65, 10.0, 10.0 0.171, -0.63, 10.0, 10.0 0.285, -0.60, 10.0, 10.0 0.399, -0.56, 10.0, 10.0 0.513, -0.55, 10.0, 10.0 0.627, -0.50, 10.0, 10.0 0.741, -0.42, 10.0, 10.0 0.855, -0.37, 10.0, 10.0 0.969, -0.23, 10.0, 10.0 1.083, 0.26, 10.0, 10.0 1.197, 0.51, 10.0, 10.0 1.311, 0.62, 10.0, 10.0 1.425, 0.85, 10.0, 10.0 1.539, 1.04, 10.0, 10.0 1.653, 1.19, 10.0, 10.0 1.767, 1.65, 10.0, 10.0